BE4
(PDF File)

PDF
  • Bright 6 digit display
  • Push-button or auto-tare
  • Excitation for up to 4 load cells
  • PC compatible version
  • Front panel setup
  • Auto or manual in-flight compensation
  • Up to 8 set-points
  • Two speed feeds

The BE 4 is a cost-efficient way of monitoring and controlling a wide range of manufacturing processes. Compact, rugged and reliable, the BE 4 can be used panel mounted or bench top. Its advanced microcomputer technology means a simple, no-fuss setup and calibration procedure via the membrane keyboard.

CALIBRATION PROCEDURE

The calibration procedure is very simple:-
To enter the calibration mode the "CAL" key must be held down as the power is applied to the unit (This prevents accidental alterations.)

1: LEARN ZERO
With the weigh hopper empty Press "CAL", "1", "CAL", "ENTER".

2: LEARN SPAN
Now place a test weight on the weigh hopper Press "CAL", "2", "CAL". "ENTER".

3: ENTER TEST WEIGHT VALUE
Press "CAL", "3", now use the number keys to enter the value the test weight represents.
The zero and span of the instrument are now set up.
The other parameters are set in a similar way.

THE BE 4 SPECIFICATION
(Basic parameters)
FRONT PANEL SELECTABLE PARAMETERS
(parameters are stored in nonvolatile EEPROM memory)
Display: 6 digit l4mm LEDS.
Sensitivity: 1 micro volt.
Loadcell Input range: -3 to +30 millivolts.
Linearity: 0.03 %.
CMR ratio: 60db.
Zero stability: 0.1 micro volt per degree Celsius.
Sampling rate: 20 per second.
Sensor supply: 10 volts DC,150 milliamps.
Dimensions: 144mm wide, 72mm high. 1O5mm deep
Panel cutout: 138mm x 67mm
Display update rate: 0.05 to 10 seconds.
Span: 1 to 30,000 micro volts per digit.
Tare: Can be anywhere from -3 to +30 millivolts.
Display resolution: 1 to 100 in steps of 1.
Outputs: 5O VDC, O.5 amp open collector npn darlington transistors.
Inputs: 5 - 30 VDC 10K impedance.
Power supply: +24 volts DC.
Decimal point: Can be set on any digit.
Filter time constant: 0.1 to 10 seconds.
 

BE 4 RELAY BOARD AND POWER SUPPLY UNIT
Din rail mounting with eight output relays rated at 240 volts, 2 amps with LED indicators. 4 x 24 volts DC inputs with LED indicators. Plant wiring terminals. +24 volt DC 500 milliamp supply. (separate power supply unit provided). Supplied with one meter input output ribbon cable to connect to the BE 4. (Dimensions L239 x W82 x H50mm).
BE4 Relay Board
24V Power Supply Unit

Home